<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>HVAC Systems Sensor Solutions | DuoMy Industrial Sensors</title>
	<atom:link href="https://www.duomy.com/industry/hvac-systems/feed/" rel="self" type="application/rss+xml" />
	<link>https://www.duomy.com/industry/hvac-systems/</link>
	<description></description>
	<lastBuildDate>Sat, 31 Oct 2026 09:56:53 +0000</lastBuildDate>
	<language>en-US</language>
	<sy:updatePeriod>
	hourly	</sy:updatePeriod>
	<sy:updateFrequency>
	1	</sy:updateFrequency>
	<generator>https://wordpress.org/?v=7.1.4</generator>

<image>
	<url>https://www.duomy.com/wp-content/uploads/2026/04/cropped-电子-32x32.png</url>
	<title>HVAC Systems Sensor Solutions | DuoMy Industrial Sensors</title>
	<link>https://www.duomy.com/industry/hvac-systems/</link>
	<width>32</width>
	<height>32</height>
</image> 
	<item>
		<title>DM-MR10 Miniature Rotary Actuator, 10 N·m</title>
		<link>https://www.duomy.com/products/dm-mr10-miniature-rotary-actuator/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:22 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-mr10-miniature-rotary-actuator/</guid>

					<description><![CDATA[<p>Compact rotary actuator with 10 N·m torque, 0.05° repeatability and RS485 control, for valve, shutter and indexing duties where a gearbox would be too large.</p>
<p>The post <a href="https://www.duomy.com/products/dm-mr10-miniature-rotary-actuator/">DM-MR10 Miniature Rotary Actuator, 10 N·m</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-MR10 provides controlled rotation in a package small enough to mount directly on a valve stem or a shutter shaft. A brushless motor drives through a low-backlash planetary stage, and an absolute encoder reports position over RS485 without a homing cycle at power-up.</p>
<p>The absolute encoder is the practical difference in valve and damper applications: after a power loss the actuator knows where it is and moves to the commanded position without driving the mechanism against a stop. Torque is limited electronically, so a jammed valve stalls the actuator instead of damaging it.</p>
<h2>Key features</h2>
<ul>
<li>10 N·m continuous torque, 25 N·m peak</li>
<li>0.05° repeatability with absolute encoder feedback</li>
<li>RS485 Modbus control, optional 0-10 V or 4-20 mA</li>
<li>Electronic torque limiting and stall detection</li>
<li>Manual override hex on the output shaft</li>
<li>IP65 housing, -10 to +60 °C operating range</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Quarter-turn valve and damper actuation</li>
<li>Optical shutter and filter wheel indexing</li>
<li>Rotary indexing tables in assembly machines</li>
<li>Adjustable orifice and louvre control</li>
</ul>
<h2>Sizing note</h2>
<p>Size on the running torque plus a 50% margin for breakaway and fouling, not on the nameplate torque alone. A valve that has not moved for six months needs more torque to break away than the datasheet friction figure suggests.</p>
<p>The post <a href="https://www.duomy.com/products/dm-mr10-miniature-rotary-actuator/">DM-MR10 Miniature Rotary Actuator, 10 N·m</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-LU200 Ultrasonic Level Sensor, 0.3-6 m</title>
		<link>https://www.duomy.com/products/dm-lu200-ultrasonic-level-sensor/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:17 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-lu200-ultrasonic-level-sensor/</guid>

					<description><![CDATA[<p>Compact ultrasonic level sensor for water, wastewater and clean liquids, 0.3-6 m range, 4-20 mA output, with temperature compensation and a 6° beam.</p>
<p>The post <a href="https://www.duomy.com/products/dm-lu200-ultrasonic-level-sensor/">DM-LU200 Ultrasonic Level Sensor, 0.3-6 m</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-LU200 is the cost-effective answer for clean water level measurement in sumps, tanks and reservoirs. It fires an acoustic pulse downward, times the echo and converts it into a level, with a built-in temperature sensor compensating for the speed of sound in air.</p>
<p>The 6° beam angle is narrow enough for a 300 mm tank opening and wide enough to tolerate a slightly off-vertical mounting. Setup is by two buttons and a display, with a 4-20 mA output that can be inverted for distance or level, which saves a configuration step when replacing a failed unit in the field.</p>
<h2>Key features</h2>
<ul>
<li>0.3-6 m range, ±0.25% FS accuracy</li>
<li>Built-in temperature compensation for speed of sound</li>
<li>4-20 mA output, invertible between level and distance</li>
<li>Two-button setup with local display</li>
<li>IP67 housing, PVC or PVDF transducer</li>
<li>Adjustable false-echo suppression for tank internals</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Sump and wet well level with pump control</li>
<li>Water tank and reservoir inventory</li>
<li>Cooling tower basin level</li>
<li>Chemical tank level for non-foaming liquids</li>
</ul>
<h2>Where ultrasonic stops working</h2>
<p>Foam, heavy vapour, condensation on the transducer and wind across an open tank all degrade an ultrasonic reading, usually by returning a plausible but wrong value rather than a fault. If any of those conditions apply, specify a radar sensor instead.</p>
<p>The post <a href="https://www.duomy.com/products/dm-lu200-ultrasonic-level-sensor/">DM-LU200 Ultrasonic Level Sensor, 0.3-6 m</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-FV40 Vortex Flow Meter for Steam and Gas, DN15-DN300</title>
		<link>https://www.duomy.com/products/dm-fv40-vortex-flow-meter/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:16 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-fv40-vortex-flow-meter/</guid>

					<description><![CDATA[<p>Vortex flow meter for saturated and superheated steam, compressed air and gases. DN15-DN300, no moving parts, 4-20 mA with HART and optional temperature compensation.</p>
<p>The post <a href="https://www.duomy.com/products/dm-fv40-vortex-flow-meter/">DM-FV40 Vortex Flow Meter for Steam and Gas, DN15-DN300</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-FV40 measures steam and gas flow using the von Kármán vortex principle: a bluff body in the flow sheds vortices at a frequency proportional to velocity, and a piezoelectric sensor downstream counts them. There are no moving parts in the flow, so the meter does not wear and does not need a strainer or a bypass.</p>
<p>With the optional integrated PT100, the meter calculates compensated mass flow for saturated steam directly, so the control system receives a mass flow value instead of volumetric flow that has to be corrected elsewhere. The display shows flow, total, temperature and pressure on two lines.</p>
<h2>Key features</h2>
<ul>
<li>DN15 to DN300, PN16 to PN40 flange connections</li>
<li>±1% of reading for liquids, ±1.5% for gases and steam</li>
<li>No moving parts, no strainer required</li>
<li>Integrated temperature compensation for saturated steam (option)</li>
<li>4-20 mA with HART 7, pulse and RS485 Modbus</li>
<li>Up to 400 °C media temperature with the high-temperature head</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Steam header and branch metering</li>
<li>Compressed air consumption by production area</li>
<li>Natural gas and process gas flow</li>
<li>Boiler feedwater and condensate measurement</li>
</ul>
<h2>Sizing note</h2>
<p>Vortex meters have a minimum Reynolds number, so an oversized meter will not register low flow. Size for the normal flow at 60-80% of range and confirm that the minimum flow stays above the meter&#8217;s lower limit; if it does not, choose a smaller size or a different technology.</p>
<p>The post <a href="https://www.duomy.com/products/dm-fv40-vortex-flow-meter/">DM-FV40 Vortex Flow Meter for Steam and Gas, DN15-DN300</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-FE150 Clamp-On Ultrasonic Flow Meter, DN15-DN600</title>
		<link>https://www.duomy.com/products/dm-fe150-clamp-on-ultrasonic-flow-meter/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:14 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-fe150-clamp-on-ultrasonic-flow-meter/</guid>

					<description><![CDATA[<p>Non-invasive clamp-on ultrasonic flow meter for DN15 to DN600 pipe, ±1% of reading, with 4-20 mA, pulse and Modbus outputs. Installs without cutting the pipe or shutting down the line.</p>
<p>The post <a href="https://www.duomy.com/products/dm-fe150-clamp-on-ultrasonic-flow-meter/">DM-FE150 Clamp-On Ultrasonic Flow Meter, DN15-DN600</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-FE150 measures flow from outside the pipe. Two transducers clamp onto the pipe wall, send an acoustic pulse diagonally through the liquid and back, and calculate flow from the transit-time difference in both directions. Nothing enters the process, so there is no pressure drop, no leak path and no shutdown to install it.</p>
<p>The controller accepts pipe outside diameter, wall thickness, material and lining, then calculates the transducer spacing itself. A mounting rail with a scale fixes the spacing and keeps it stable, and the supplied wall-thickness gauge removes the second-largest source of field error after straight run.</p>
<h2>Key features</h2>
<ul>
<li>DN15 to DN600, ±1% of reading in calibrated conditions</li>
<li>Bidirectional measurement, totaliser and batch functions</li>
<li>4-20 mA, pulse, relay and RS485 Modbus outputs</li>
<li>Clamp-on installation with mounting rail and wall-thickness gauge</li>
<li>Data logging for up to 60 days at 1-minute intervals</li>
<li>Battery or 24 VDC powered versions</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Flow verification and energy allocation on existing mains</li>
<li>Chilled and hot water loop balancing</li>
<li>Temporary flow surveys and leak detection</li>
<li>Process cooling water in semiconductor and data centre facilities</li>
</ul>
<h2>Installation requirements</h2>
<p>Allow ten pipe diameters upstream and five downstream, keep the transducers on the side of a horizontal pipe rather than the top, and make sure the pipe is full. Clamp-on meters fail predictably when the pipe is partially full or when a liner separates the transducer from the liquid.</p>
<p>The post <a href="https://www.duomy.com/products/dm-fe150-clamp-on-ultrasonic-flow-meter/">DM-FE150 Clamp-On Ultrasonic Flow Meter, DN15-DN600</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-TS100 PT100 RTD Probe, -50 to +400 °C</title>
		<link>https://www.duomy.com/products/dm-ts100-pt100-rtd-probe/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:12 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-ts100-pt100-rtd-probe/</guid>

					<description><![CDATA[<p>Class A PT100 probe in a 6 mm 316L sheath, 4-wire connection, -50 to +400 °C, with G1/2 thread and spring-loaded insertion for process and utility temperature measurement.</p>
<p>The post <a href="https://www.duomy.com/products/dm-ts100-pt100-rtd-probe/">DM-TS100 PT100 RTD Probe, -50 to +400 °C</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-TS100 is a general-purpose platinum resistance probe for process and utility temperature measurement. The element is a Class A PT100 in a 6 mm 316L stainless sheath, wired 4-wire so the lead resistance cancels out and the reading does not change when the cable length changes.</p>
<p>The probe is available with a fixed G1/2 thread or a spring-loaded compression fitting that holds the tip against the pipe wall or thermowell bottom. Spring loading removes the air gap that causes slow and low readings on immersion probes, which is the most common installation error in temperature measurement.</p>
<h2>Key features</h2>
<ul>
<li>Class A PT100 element, ±0.15 °C at 0 °C, 4-wire connection</li>
<li>6 mm 316L stainless sheath, length 100 to 500 mm</li>
<li>Response time t90 = 8 s in flowing water</li>
<li>G1/2 thread, spring-loaded compression fitting or clamp connection</li>
<li>-50 to +400 °C range, IP67 connection head</li>
<li>Optional 3-point calibration certificate</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Hot water and steam line temperature</li>
<li>Bearing and gearbox temperature monitoring</li>
<li>HVAC immersion and duct temperature</li>
<li>Sanitary process temperature with clamp connection</li>
</ul>
<h2>Selection note</h2>
<p>Immersion depth should be at least ten sheath diameters in liquid and more in gas. A 6 mm probe fitted into a 30 mm pocket will read the pocket wall, not the process, and the error grows as the pipe temperature diverges from the media temperature.</p>
<p>The post <a href="https://www.duomy.com/products/dm-ts100-pt100-rtd-probe/">DM-TS100 PT100 RTD Probe, -50 to +400 °C</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-PD100 Differential Pressure Transmitter, 0-10 kPa</title>
		<link>https://www.duomy.com/products/dm-pd100-differential-pressure-transmitter/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:11 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-pd100-differential-pressure-transmitter/</guid>

					<description><![CDATA[<p>Low-range differential pressure transmitter for filter monitoring, cleanroom cascades and flow across an orifice plate. 0-10 kPa, 0.075% FS, static line pressure to 160 bar.</p>
<p>The post <a href="https://www.duomy.com/products/dm-pd100-differential-pressure-transmitter/">DM-PD100 Differential Pressure Transmitter, 0-10 kPa</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-PD100 measures the difference between two pressure ports rather than a single line pressure, which is what filter monitoring, room pressure cascades and orifice-plate flow measurement actually require. The two-port capsule is machined from a single stainless block, so thermal gradients across the body do not create the offset that plagues assembled differential sensors.</p>
<p>Accuracy is 0.075% of span, and the static line pressure rating of 160 bar means the transmitter can sit on a high-pressure filter housing while still resolving a 2 kPa pressure drop. The 4-20 mA output is loop-powered, and the zero and span are adjustable from the front panel without opening the housing.</p>
<h2>Key features</h2>
<ul>
<li>0-10 kPa differential range with 160 bar static line pressure</li>
<li>0.075% FS accuracy including thermal effect over the compensated range</li>
<li>Single-block stainless capsule, no internal elastomer seals</li>
<li>Front-accessible zero and span adjustment</li>
<li>Two 1/4 NPT or G1/4 process ports with bleed valves</li>
<li>Optional three-valve manifold for in-service zeroing</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Filter and strainer differential pressure monitoring</li>
<li>Cleanroom and corridor pressure cascade control</li>
<li>Orifice plate and Venturi flow measurement</li>
<li>Tank level by hydrostatic differential measurement</li>
</ul>
<h2>Installation note</h2>
<p>Mount the transmitter below the tap points for liquid service and above them for gas, with equal-length impulse lines sloping continuously to the process. Unequal line length or a trapped condensate slug shifts the zero, and no amount of configuration will remove it.</p>
<p>The post <a href="https://www.duomy.com/products/dm-pd100-differential-pressure-transmitter/">DM-PD100 Differential Pressure Transmitter, 0-10 kPa</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-PS500 Compact Pressure Switch, 0.5-10 bar</title>
		<link>https://www.duomy.com/products/dm-ps500-pressure-switch/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:11 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-ps500-pressure-switch/</guid>

					<description><![CDATA[<p>Mechanical pressure switch with adjustable set point from 0.5 to 10 bar, SPDT contact rated 5 A, and a stainless body for pump and compressor interlock duty.</p>
<p>The post <a href="https://www.duomy.com/products/dm-ps500-pressure-switch/">DM-PS500 Compact Pressure Switch, 0.5-10 bar</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-PS500 is a mechanical pressure switch for interlock and alarm duty where a continuous analogue signal is not needed. A stainless diaphragm acts on a snap-action microswitch, so the contact changes state decisively at the set point with no chatter at the threshold, which matters when the switch drives a contactor or a PLC input.</p>
<p>The set point is adjusted by a screw under the protective cap and the differential is fixed at 15% of the set point. The body is stainless steel with a G1/4 process connection and an IP67 housing, and the electrical connection is a DIN 43650 valve connector that keeps the terminal block sealed.</p>
<h2>Key features</h2>
<ul>
<li>Adjustable set point 0.5-10 bar, fixed hysteresis 15% of set point</li>
<li>SPDT snap-action contact rated 5 A at 250 VAC</li>
<li>Stainless steel body and diaphragm, G1/4 process connection</li>
<li>DIN 43650 connector with IP67 protection</li>
<li>No supply voltage required, suitable for pure interlock circuits</li>
<li>Repeatability within 2% of set point over 100,000 cycles</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Pump start and stop on pressure</li>
<li>Compressor low-pressure and high-pressure interlock</li>
<li>Filter clogging alarm</li>
<li>Machine guard and pneumatic clamp confirmation</li>
</ul>
<h2>When to use a switch instead of a transmitter</h2>
<p>If the control system only needs a discrete signal at a threshold, a mechanical switch removes the analogue input card, the scaling and the calibration interval. If the threshold will change with product or season, a transmitter with a configurable set point is the better long-term choice.</p>
<p>The post <a href="https://www.duomy.com/products/dm-ps500-pressure-switch/">DM-PS500 Compact Pressure Switch, 0.5-10 bar</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		