<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>Food &amp; Beverage Sensor Solutions | DuoMy Industrial Sensors</title>
	<atom:link href="https://www.duomy.com/industry/food-beverage/feed/" rel="self" type="application/rss+xml" />
	<link>https://www.duomy.com/industry/food-beverage/</link>
	<description></description>
	<lastBuildDate>Sat, 31 Oct 2026 09:57:08 +0000</lastBuildDate>
	<language>en-US</language>
	<sy:updatePeriod>
	hourly	</sy:updatePeriod>
	<sy:updateFrequency>
	1	</sy:updateFrequency>
	<generator>https://wordpress.org/?v=7.1.4</generator>

<image>
	<url>https://www.duomy.com/wp-content/uploads/2026/04/cropped-电子-32x32.png</url>
	<title>Food &amp; Beverage Sensor Solutions | DuoMy Industrial Sensors</title>
	<link>https://www.duomy.com/industry/food-beverage/</link>
	<width>32</width>
	<height>32</height>
</image> 
	<item>
		<title>DM-CJ08 8-Port M12 Junction Box, IP67</title>
		<link>https://www.duomy.com/products/dm-cj08-junction-box/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:25 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-cj08-junction-box/</guid>

					<description><![CDATA[<p>Passive 8-port M12 junction box that consolidates sensor wiring into a single home-run cable, with LED indication per port and an IP67 PBT housing.</p>
<p>The post <a href="https://www.duomy.com/products/dm-cj08-junction-box/">DM-CJ08 8-Port M12 Junction Box, IP67</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-CJ08 collects eight sensor cables into one multi-core home run, which reduces the number of cables entering a cabinet from eight to one and makes a machine section easier to isolate and service. Each port has an LED so a technician can see the signal state without opening the box.</p>
<p>The housing is PBT with a gasket and stainless screws, rated IP67 in the mated condition. Ports are 3, 4 or 5-pin M12, and the home run is a fixed 5 m or 10 m cable with a connector or flying leads.</p>
<h2>Key features</h2>
<ul>
<li>8 x M12 ports, 3/4/5-pin configuration</li>
<li>Single home-run cable to the cabinet</li>
<li>Per-port LED indication</li>
<li>IP67 PBT housing with stainless fasteners</li>
<li>2 A per port, 30 V AC/DC</li>
<li>Optional stainless housing for washdown and chemical areas</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Sensor clusters on conveyor sections</li>
<li>End-effector and gripper wiring consolidation</li>
<li>Pump station instrument collection</li>
<li>Machine sections with frequent changeover</li>
</ul>
<h2>Selection note</h2>
<p>A passive box carries the signals only; it does not condition or isolate them. If the sensors are far from the cabinet or the environment is electrically noisy, use a master with per-port diagnostics, or add an isolating conditioner at the cabinet end.</p>
<p>The post <a href="https://www.duomy.com/products/dm-cj08-junction-box/">DM-CJ08 8-Port M12 Junction Box, IP67</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-SD24 Loop-Powered Digital Indicator with 2 Relays</title>
		<link>https://www.duomy.com/products/dm-sd24-loop-powered-indicator/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:24 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-sd24-loop-powered-indicator/</guid>

					<description><![CDATA[<p>Two-wire loop-powered indicator that shows the 4-20 mA value at the machine and provides two configurable alarm relays, without an additional power supply.</p>
<p>The post <a href="https://www.duomy.com/products/dm-sd24-loop-powered-indicator/">DM-SD24 Loop-Powered Digital Indicator with 2 Relays</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-SD24 takes its power from the current loop it is measuring, so installing it means breaking the loop and inserting the indicator, nothing more. It displays the scaled value in engineering units and provides two relays that can be set as high, low or window alarms with adjustable hysteresis and delay.</p>
<p>That combination replaces a separate display and trip amplifier in many panels. It is particularly useful on remote or skid-mounted equipment where an operator needs to see the value and where a local alarm must act even if the control system is offline.</p>
<h2>Key features</h2>
<ul>
<li>Two-wire, loop-powered, no separate supply required</li>
<li>4-digit display with configurable engineering units and scaling</li>
<li>Two relays configurable as high, low or window alarm</li>
<li>Adjustable hysteresis and 0-60 s alarm delay</li>
<li>IP65 front face for panel or field mounting</li>
<li>Voltage drop of only 2.5 V, minimising loop burden</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Local readout on pump and valve skids</li>
<li>Over-temperature and dry-run alarms</li>
<li>Level indication on remote tanks</li>
<li>Flow totalising display at a metering point</li>
</ul>
<h2>Loop budget note</h2>
<p>A two-wire indicator adds to the loop resistance. Check that the transmitter&#8217;s minimum supply voltage plus the indicator&#8217;s voltage drop plus the cable and sense resistor still falls below the available supply, especially on 12 V loops.</p>
<p>The post <a href="https://www.duomy.com/products/dm-sd24-loop-powered-indicator/">DM-SD24 Loop-Powered Digital Indicator with 2 Relays</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-CB05 M12 5-Pin Shielded Sensor Cable, 5 m PUR</title>
		<link>https://www.duomy.com/products/dm-cb05-m12-sensor-cable/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:24 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-cb05-m12-sensor-cable/</guid>

					<description><![CDATA[<p>Overmoulded M12 5-pin shielded cordset, 5 m PUR jacket, IP69K, straight or angled, for sensor connections in coolant and washdown areas.</p>
<p>The post <a href="https://www.duomy.com/products/dm-cb05-m12-sensor-cable/">DM-CB05 M12 5-Pin Shielded Sensor Cable, 5 m PUR</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-CB05 is an overmoulded five-pin cordset for standard sensor connections. The moulded body seals the conductor entry permanently, which removes the gland that is responsible for most water ingress in field-wired connectors, and the PUR jacket resists coolant, oil and repeated flexing.</p>
<p>Shielding is included as standard, because the cost difference against unshielded cable is small and the benefit in any panel with a drive is large. The shield is bonded to the coupling nut so it terminates at the sensor housing and at the panel gland.</p>
<h2>Key features</h2>
<ul>
<li>M12 A-coded, 5-pin, straight or 90° angled</li>
<li>Shielded construction with braid coverage over 85%</li>
<li>PUR jacket resistant to coolant, oil and UV</li>
<li>IP69K in the mated condition</li>
<li>2 A per contact, 30 V AC/DC rated</li>
<li>Available in 0.3, 2, 5 and 10 m lengths from stock</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Sensor and actuator connections on machine tools</li>
<li>Washdown areas in food and beverage plants</li>
<li>Gripper and end-effector wiring</li>
<li>IO-Link device connections at 230 kbit/s</li>
</ul>
<h2>Installation note</h2>
<p>Tighten the coupling nut by hand and then a quarter turn; over-tightening distorts the seal and under-tightening lets water in. Respect the bend radius at the connector body, because the failure point on a moulded cordset is where the cable leaves the moulding.</p>
<p>The post <a href="https://www.duomy.com/products/dm-cb05-m12-sensor-cable/">DM-CB05 M12 5-Pin Shielded Sensor Cable, 5 m PUR</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-PC18 M18 Capacitive Proximity Sensor, 8 mm, IO-Link</title>
		<link>https://www.duomy.com/products/dm-pc18-capacitive-proximity-sensor/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:19 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-pc18-capacitive-proximity-sensor/</guid>

					<description><![CDATA[<p>M18 capacitive proximity sensor that detects plastics, glass, wood and liquids, with 8 mm adjustable sensing distance, IO-Link parameterisation and PNP output.</p>
<p>The post <a href="https://www.duomy.com/products/dm-pc18-capacitive-proximity-sensor/">DM-PC18 M18 Capacitive Proximity Sensor, 8 mm, IO-Link</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-PC18 detects what an inductive sensor cannot: plastic containers, glass bottles, cardboard, wood and bulk material. The sensing field is capacitive, so any material with a dielectric constant above about 1.5 will trigger it, and the sensitivity potentiometer or IO-Link parameter sets the threshold for the specific product.</p>
<p>The IO-Link version matters on lines with frequent product changes. Instead of an operator adjusting a potentiometer behind a guard, the switching threshold and the output logic are stored in the recipe and downloaded over IO-Link when the product changes.</p>
<h2>Key features</h2>
<ul>
<li>8 mm adjustable sensing distance, non-flush mountable</li>
<li>Detects plastics, glass, wood, paper and liquids</li>
<li>IO-Link 1.1 parameterisation plus PNP switching output</li>
<li>Sensitivity adjustment by potentiometer or IO-Link</li>
<li>IP67 PBT housing with M12 connector</li>
<li>Switching frequency 100 Hz, suited to presence detection</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Bottle, cap and label presence on filling lines</li>
<li>Level detection through a plastic tank wall</li>
<li>Cardboard and wood board detection in packaging</li>
<li>Product changeover with recipe-based thresholds</li>
</ul>
<h2>Application note</h2>
<p>Capacitive sensors are affected by humidity and by product residue on the face. Mount them where the face stays clear, and use IO-Link diagnostics to detect a threshold that is drifting before it causes a missed detection.</p>
<p>The post <a href="https://www.duomy.com/products/dm-pc18-capacitive-proximity-sensor/">DM-PC18 M18 Capacitive Proximity Sensor, 8 mm, IO-Link</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-PX12 M12 Inductive Proximity Sensor, 4 mm, IP69K</title>
		<link>https://www.duomy.com/products/dm-px12-inductive-proximity-sensor/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:18 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-px12-inductive-proximity-sensor/</guid>

					<description><![CDATA[<p>M12 stainless steel inductive proximity sensor with 4 mm flush sensing distance, PNP NO output, IP69K rating and an M12 connector for machine and washdown duty.</p>
<p>The post <a href="https://www.duomy.com/products/dm-px12-inductive-proximity-sensor/">DM-PX12 M12 Inductive Proximity Sensor, 4 mm, IP69K</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-PX12 is the workhorse of the range: an M12 barrel sensor in a 304 stainless housing, flush mountable, with a 4 mm sensing distance on mild steel. The oscillator, output stage and protection circuitry are potted into the barrel, so vibration and moisture have nothing to work loose.</p>
<p>The IP69K rating applies to the sensor and its connector together, which is why the M12 connector version is specified for washdown areas rather than a cable tail with a gland. Output is PNP normally open, with NPN and two-wire versions available in the same housing.</p>
<h2>Key features</h2>
<ul>
<li>4 mm flush sensing distance on mild steel, 2 mm on stainless</li>
<li>PNP NO output, 200 mA, short-circuit and reverse-polarity protected</li>
<li>IP69K with an IP69K cordset fitted</li>
<li>1 kHz switching frequency, 10-30 VDC supply</li>
<li>304 stainless barrel, -25 to +70 °C ambient</li>
<li>LED indication visible from three sides</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Clamp, slide and end-stop position on machine tools</li>
<li>Part presence on conveyors and transfer stations</li>
<li>Gripper and tool-changer confirmation</li>
<li>Door and guard position on washdown equipment</li>
</ul>
<h2>Mounting note</h2>
<p>Flush mountable sensors can be embedded in metal without a free zone, but leave at least one sensing distance between two adjacent sensors to avoid mutual interference. On aluminium or stainless targets, expect the sensing distance to fall by 30-50% and specify an extended-range model if the gap is tight.</p>
<p>The post <a href="https://www.duomy.com/products/dm-px12-inductive-proximity-sensor/">DM-PX12 M12 Inductive Proximity Sensor, 4 mm, IP69K</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-LF120 Capacitive Level Switch for Liquids and Powders</title>
		<link>https://www.duomy.com/products/dm-lf120-capacitive-level-switch/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:17 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-lf120-capacitive-level-switch/</guid>

					<description><![CDATA[<p>Capacitive point-level switch for liquids, granules and powders, with adjustable sensitivity, PNP or relay output and a stainless or PTFE-coated rod probe.</p>
<p>The post <a href="https://www.duomy.com/products/dm-lf120-capacitive-level-switch/">DM-LF120 Capacitive Level Switch for Liquids and Powders</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-LF120 detects the presence or absence of material at a single point. A rod probe forms one plate of a capacitor and the vessel wall the other, so when product covers the rod the capacitance changes and the output switches. There are no moving parts and nothing to jam, which is why capacitive switches are used on powders and sticky media where a float would fail.</p>
<p>Sensitivity is adjustable to compensate for a low dielectric constant or for build-up on the probe. The standard output is PNP, with relay and NAMUR versions available for interlock circuits and hazardous areas.</p>
<h2>Key features</h2>
<ul>
<li>Point-level detection for liquids, granules and powders</li>
<li>Adjustable sensitivity for media with low dielectric constant</li>
<li>PNP, relay or NAMUR output</li>
<li>Stainless steel or PTFE-coated rod, lengths 100-1,000 mm</li>
<li>Build-up compensation via sensitivity adjustment</li>
<li>IP67 with M12 connector</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>High-level alarm on tanks and silos</li>
<li>Dry-run protection on pumps and dosing systems</li>
<li>Powder and granule presence in hoppers</li>
<li>Interface detection between two liquids</li>
</ul>
<h2>Selection note</h2>
<p>Capacitive switching depends on the dielectric constant of the medium. Water at 80 is easy; oils at 2.2 and plastic pellets at 2.0 are marginal and need a coated probe or a different technology. State the medium when ordering so the probe length and sensitivity are set at the factory.</p>
<p>The post <a href="https://www.duomy.com/products/dm-lf120-capacitive-level-switch/">DM-LF120 Capacitive Level Switch for Liquids and Powders</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-LR60 80 GHz Radar Level Transmitter, 0-30 m</title>
		<link>https://www.duomy.com/products/dm-lr60-radar-level-transmitter/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:16 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-lr60-radar-level-transmitter/</guid>

					<description><![CDATA[<p>80 GHz non-contact radar level transmitter with 0-30 m range and ±3 mm accuracy. Narrow 4° beam, unaffected by vapour and foam, with 4-20 mA / HART and Bluetooth setup.</p>
<p>The post <a href="https://www.duomy.com/products/dm-lr60-radar-level-transmitter/">DM-LR60 80 GHz Radar Level Transmitter, 0-30 m</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-LR60 uses an 80 GHz frequency-modulated continuous-wave radar to measure the distance to a liquid or solid surface without contact. The short wavelength gives a narrow 4° beam, which is what allows the transmitter to be mounted in a tank with agitators, heating coils and inlet streams without picking up a reflection from any of them.</p>
<p>Because the measurement is electromagnetic rather than acoustic, vapour, dust, foam and wind have far less effect than they do on an ultrasonic sensor. Setup is done over Bluetooth from a phone or over HART from the control system, and the empty and full calibration can be entered as distances rather than as percentages, which removes a common source of configuration error.</p>
<h2>Key features</h2>
<ul>
<li>0-30 m range with ±3 mm accuracy</li>
<li>80 GHz FMCW, 4° beam angle</li>
<li>Unaffected by vapour, dust and most foam</li>
<li>4-20 mA with HART 7 and Bluetooth configuration</li>
<li>PTFE or PFA antenna for corrosive media</li>
<li>Process temperature -40 to +150 °C, pressure -1 to 40 bar</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Wet wells, sumps and pump stations</li>
<li>Fermentation and buffer tanks with foam</li>
<li>Silo and hopper inventory for powders and pellets</li>
<li>Chemical storage tanks with corrosive vapours</li>
</ul>
<h2>Mounting note</h2>
<p>Keep the antenna clear of the tank wall by at least 100 mm and away from the inlet stream. A nozzle that protrudes more than its own diameter into the tank creates a false echo that no configuration can remove, so shorten the nozzle or use a flush antenna.</p>
<p>The post <a href="https://www.duomy.com/products/dm-lr60-radar-level-transmitter/">DM-LR60 80 GHz Radar Level Transmitter, 0-30 m</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-FT80 Turbine Flow Meter, 1/2&#8243;-2&#8243;</title>
		<link>https://www.duomy.com/products/dm-ft80-turbine-flow-meter/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:15 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-ft80-turbine-flow-meter/</guid>

					<description><![CDATA[<p>Turbine flow meter for clean low-viscosity liquids on 1/2" to 2" lines, ±0.5% of reading, with pulse, 4-20 mA and local totaliser in a compact stainless body.</p>
<p>The post <a href="https://www.duomy.com/products/dm-ft80-turbine-flow-meter/">DM-FT80 Turbine Flow Meter, 1/2&#8243;-2&#8243;</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-FT80 is a small-line turbine meter for clean, low-viscosity liquids: fuels, solvents, water, glycol and light oils. A free-running rotor turns in proportion to flow, and a Hall-effect sensor picks up the blade passage without contact, so there is no wear element in the signal path and the pulse output drops straight into a totaliser or PLC counter.</p>
<p>The body is 316L stainless with a tungsten carbide shaft and a sapphire bearing on the standard version, which keeps the calibration stable in clean service. Each meter is wet-calibrated, and the K factor is marked on the body and stored in the electronics where a display version is fitted.</p>
<h2>Key features</h2>
<ul>
<li>±0.5% of reading over the calibrated range, 10:1 turndown</li>
<li>1/2&#8243; to 2&#8243; line sizes, BSP or NPT connections</li>
<li>Tungsten carbide shaft and sapphire bearing</li>
<li>Pulse, 4-20 mA and local totaliser options</li>
<li>Wet-calibrated with the K factor marked on the housing</li>
<li>-20 to +120 °C media temperature, 40 bar rating</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Diesel, kerosene and lubricant dispensing</li>
<li>Coolant and glycol filling on assembly lines</li>
<li>Chemical dosing and batch totalising</li>
<li>Test rig fuel consumption measurement</li>
</ul>
<h2>Application limits</h2>
<p>A turbine meter needs clean liquid. Grit, fibres or crystallising media will wear or seize the rotor, and the calibration will drift without any alarm. If the media is not clean, use an electromagnetic or clamp-on ultrasonic meter instead, even at a higher cost.</p>
<p>The post <a href="https://www.duomy.com/products/dm-ft80-turbine-flow-meter/">DM-FT80 Turbine Flow Meter, 1/2&#8243;-2&#8243;</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-TT200 Head-Mount Temperature Transmitter, 4-20 mA / HART</title>
		<link>https://www.duomy.com/products/dm-tt200-head-mount-transmitter/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:13 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-tt200-head-mount-transmitter/</guid>

					<description><![CDATA[<p>Universal head-mount transmitter for RTD and thermocouple inputs, 4-20 mA with HART 7, 1,500 V isolation and 0.1 °C measurement resolution in a DIN B head.</p>
<p>The post <a href="https://www.duomy.com/products/dm-tt200-head-mount-transmitter/">DM-TT200 Head-Mount Temperature Transmitter, 4-20 mA / HART</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-TT200 converts an RTD or thermocouple signal into a 4-20 mA loop inside the connection head, metres away from the measurement point. That short analogue path is the whole point: the low-level sensor signal stays inside a shielded head instead of travelling down a cable next to a drive, and the control system receives a robust current loop.</p>
<p>The input is universal and configured by software, covering PT100, PT1000, Ni1000, thermocouple types K, J, T, E, N, R, S, B, and millivolt or resistance inputs. Sensor matching (Callendar-Van Dusen coefficients) can be entered for a specific probe, which brings a standard Class A element closer to a calibrated pair without buying a tighter element.</p>
<h2>Key features</h2>
<ul>
<li>Universal input: RTD, thermocouple, mV, resistance</li>
<li>4-20 mA output with HART 7 digital communication</li>
<li>1,500 VAC galvanic isolation between input and output</li>
<li>Sensor matching via CVD coefficients for individual probes</li>
<li>Sensor break and short-circuit detection with configurable drive</li>
<li>Fits DIN B connection heads, 34 mm diameter, 22 mm height</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Process temperature loops on RTD and thermocouple probes</li>
<li>Retrofit of direct-wired RTDs onto an existing 4-20 mA card</li>
<li>Hazardous-area loops with intrinsic safety barriers</li>
<li>Sanitary probe assemblies in food and pharmaceutical service</li>
</ul>
<h2>Commissioning note</h2>
<p>Configure the input type and range before installation, then verify the loop current at two points. A transmitter configured for a 3-wire PT100 on a 4-wire probe will read a plausible but wrong value, which is harder to find later than an outright failure.</p>
<p>The post <a href="https://www.duomy.com/products/dm-tt200-head-mount-transmitter/">DM-TT200 Head-Mount Temperature Transmitter, 4-20 mA / HART</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>DM-TS100 PT100 RTD Probe, -50 to +400 °C</title>
		<link>https://www.duomy.com/products/dm-ts100-pt100-rtd-probe/</link>
		
		<dc:creator><![CDATA[]]></dc:creator>
		<pubDate>Sat, 31 Oct 2026 09:33:12 +0000</pubDate>
				<guid isPermaLink="false">https://www.duomy.com/products/dm-ts100-pt100-rtd-probe/</guid>

					<description><![CDATA[<p>Class A PT100 probe in a 6 mm 316L sheath, 4-wire connection, -50 to +400 °C, with G1/2 thread and spring-loaded insertion for process and utility temperature measurement.</p>
<p>The post <a href="https://www.duomy.com/products/dm-ts100-pt100-rtd-probe/">DM-TS100 PT100 RTD Probe, -50 to +400 °C</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></description>
										<content:encoded><![CDATA[<h2>Overview</h2>
<p>The DM-TS100 is a general-purpose platinum resistance probe for process and utility temperature measurement. The element is a Class A PT100 in a 6 mm 316L stainless sheath, wired 4-wire so the lead resistance cancels out and the reading does not change when the cable length changes.</p>
<p>The probe is available with a fixed G1/2 thread or a spring-loaded compression fitting that holds the tip against the pipe wall or thermowell bottom. Spring loading removes the air gap that causes slow and low readings on immersion probes, which is the most common installation error in temperature measurement.</p>
<h2>Key features</h2>
<ul>
<li>Class A PT100 element, ±0.15 °C at 0 °C, 4-wire connection</li>
<li>6 mm 316L stainless sheath, length 100 to 500 mm</li>
<li>Response time t90 = 8 s in flowing water</li>
<li>G1/2 thread, spring-loaded compression fitting or clamp connection</li>
<li>-50 to +400 °C range, IP67 connection head</li>
<li>Optional 3-point calibration certificate</li>
</ul>
<h2>Typical applications</h2>
<ul>
<li>Hot water and steam line temperature</li>
<li>Bearing and gearbox temperature monitoring</li>
<li>HVAC immersion and duct temperature</li>
<li>Sanitary process temperature with clamp connection</li>
</ul>
<h2>Selection note</h2>
<p>Immersion depth should be at least ten sheath diameters in liquid and more in gas. A 6 mm probe fitted into a 30 mm pocket will read the pocket wall, not the process, and the error grows as the pipe temperature diverges from the media temperature.</p>
<p>The post <a href="https://www.duomy.com/products/dm-ts100-pt100-rtd-probe/">DM-TS100 PT100 RTD Probe, -50 to +400 °C</a> appeared first on <a href="https://www.duomy.com">DuoMy Sensing</a>.</p>
]]></content:encoded>
					
		
		