AC Current Transducer, 0–50 A True RMS to 4–20 mA, DIN Rail
DIN-rail AC current transducer, 0 to 50 A true RMS input, 4 to 20 mA output, 1% accuracy. Reads distorted waveforms correctly where an averaging meter under-reports by 20 percent or more.
| Parameter | Value | Unit |
|---|---|---|
| Input range | 0 to 50 | A AC, true RMS |
| Frequency | 45 to 65 | Hz |
| Output signal | 4 to 20 | mA |
| Accuracy | ±1 | % of full scale |
| Supply voltage | 24 | V DC, 18 to 30 V |
| Response time | 300 | ms |
| Overload | 120 | % continuous, 200% for 1 s |
| Isolation | 2.5 | kV AC |
| Mounting | 35 mm DIN rail | |
| Operating temperature | −20 to +60 | °C |
Overview
True RMS matters when the load is not a clean sine wave. A variable-frequency drive, a switched-mode supply or a phase-angle controller draws a current with a high crest factor, and an averaging meter calibrated for sine waves reads low by 10 to 30 percent. The protection threshold then trips late or never.
The trade-off is response time. True RMS conversion needs a measurement window, typically a few hundred milliseconds, so the output lags the actual current. For overload protection that is acceptable; for cycle-by-cycle current limiting it is not, and a shunt or Hall sensor is the correct choice.
Key features
- True RMS measurement, accurate on distorted waveforms
- 0 to 50 A input, 4 to 20 mA output
- 2.5 kV isolation between the primary and the loop
- 120% continuous overload without saturation
- DIN rail mounting with screw terminals
Typical applications
- Motor and pump load monitoring
- VFD-driven equipment current feedback
- Heater and compressor run detection
- Energy submetering on distorted loads
Selection note
Do not use a true RMS transducer for fast protection. The 300 ms response is fine for trend and alarm thresholds but far too slow for short-circuit or phase-loss detection, which needs a dedicated protection relay.
Ordering
Send the current range, waveform type, response time and output signal. We confirm RMS versus instantaneous sensing, then quote.