DM-VT-DC-600V
Ask about this product
Send your application details and get a specification answer within one business day.
Split-Core Current Transformer, 100 A / 50 mA, Class 1
Split-core AC current transformer, 100 A primary to 50 mA secondary, class 1 accuracy, 50/60 Hz. Clamps around an existing cable without disconnecting it, for retrofit metering and load monitoring.
| Parameter | Value | Unit |
|---|---|---|
| Primary current | 100 | A AC |
| Secondary output | 50 | mA AC |
| Ratio | 2000:1 | |
| Accuracy class | 1 | per IEC 61869-2 |
| Frequency | 50 / 60 | Hz |
| Burden | 10 | Ω maximum |
| Dielectric strength | 3 | kV AC, 1 minute |
| Cable aperture | 16 | mm diameter |
| Lead length | 1 | m, flying leads |
| Operating temperature | −20 to +60 | °C |
Overview
A split-core transformer is installed around a cable that is already carrying current. The two halves clamp together, the magnetic circuit closes, and the load can be measured without shutting down the line. That installation advantage is the entire reason the part exists.
The output is a current, not a voltage, and it must never be left open-circuited while the primary carries current. An open secondary develops a high voltage across its own terminals and destroys the winding. Fit a burden resistor or a shorting terminal block before clamping it on.
Key features
- Clamps around existing cable, no disconnection required
- 100 A to 50 mA, 2000:1 ratio
- Class 1 accuracy for billing-grade submetering
- 3 kV dielectric strength between primary and secondary
- 1 m flying leads, no separate terminal block
Typical applications
- Submetering and energy allocation
- Pump and compressor load monitoring
- Retrofit power measurement
- Overcurrent and no-load detection
Selection note
Never open the secondary while the primary is energised. Fit a burden resistor across the leads before installation, or use a shorting block, and only remove it after the primary is isolated.
Ordering
Send the cable diameter, primary current range and meter input type. We confirm ratio, burden and accuracy class, then quote.
No documents attached yet.
Request documentation →Related products
View allDM-CT-AC-50A-RMS
AC Current Transducer, 0–50 A True RMS to 4–20 mA, DIN Rail
DM-SHT-1M0-10W