DC Voltage Transducer, 0–600 V to 4–20 mA, DIN Rail
DIN-rail DC voltage transducer, 0 to 600 V input, 4 to 20 mA output, 0.5% of full scale, 2.5 kV isolation. Converts a high-voltage bus into a loop signal a PLC can read without an isolation amplifier on the card.
| Parameter | Value | Unit |
|---|---|---|
| Input range | 0 to 600 | V DC |
| Output signal | 4 to 20 | mA, two-wire loop |
| Accuracy | ±0.5 | % of full scale |
| Isolation | 2.5 | kV AC, input to output |
| Supply voltage | 24 | V DC nominal, 18 to 30 V |
| Response time | 200 | ms |
| Load resistance | 500 | Ω maximum |
| Mounting | 35 mm DIN rail | |
| Termination | Screw terminals, 2.5 mm² | |
| Operating temperature | −20 to +60 | °C |
Overview
A 600 V DC bus cannot be wired into an analogue input card. The card measures 0 to 10 V or 4 to 20 mA and has no isolation to speak of, so the transducer does two jobs at once: it scales the voltage down and it puts 2.5 kV of galvanic isolation between the bus and the control system.
The 4 to 20 mA loop is chosen over a voltage output because current does not drop across cable resistance. A 0 to 10 V signal over 200 m of cable loses a measurable fraction in the loop resistance; 4 to 20 mA reads the same at both ends, and a broken wire shows up as 0 mA rather than as a valid zero reading.
Key features
- 0 to 600 V DC input, 4 to 20 mA two-wire output
- 2.5 kV isolation between input and output
- 0.5% of full scale accuracy
- 35 mm DIN rail mounting with screw terminals
- Loop-powered, no separate auxiliary supply on the output side
Typical applications
- DC bus and battery bank monitoring
- Solar string and inverter voltage feedback
- Telecom and UPS plant monitoring
- PLC analogue input conditioning
Selection note
Check the loop supply against the total burden. A 500 Ω load plus cable resistance at 20 mA needs at least 20 V at the transmitter terminals, which is close to the limit of a 24 V supply with a long cable run.
Ordering
Send the input range, output signal, loop supply and isolation requirement. We confirm the scaling and burden, then quote.